Ethernet Errors
Error Message Contents Solution
0 Normal  
200 Failed in send request Check cable connection and network table setting of the target station.
201 Send error Check that the setting on the target station is consistent with the network table setting.
202 Internal port error The communication unit is in the older version or is faulty.
204 TCP connection over The number of connections reaches the maximum, and no more connection is possible. Check the communication lines.
205 TCP connection error Connection cannot be established. Check the communication lines, or turn the power off and on.
206 TCP connection end error TCP communication disconnection has failed. Check that the communication partner with the V7 series is present on the line.
207 TCP send error TCP communication has failed.
Check the communication lines.
350 Send buffer full The line is busy. Consult the network administrator of your company.
The communication unit is in the older version or is faulty.
351 IC receive buffer overflow
352 Driver receive buffer overflow
801 Receive processing error
Link down error
Check the HUB or the link confirmation LED on the communication unit. If the LED is not on, check cable connection and the port setting on the network table.
802 Transceiver error Check the transceiver and cable connection.
900 No IP address at local port Check that the IP address of the local port is set on the network table. Check if the same IP address is set on the network.
901 Duplicated IP address error
902 Send socket ID error (error that may occur when V7i LAN port is used) Turn the power off and back it on. If the problem persists, contact your local distributor.
1000 Ethernet I/F unit not mounted Check whether the Ethernet I/F unit is mounted correctly, and then turn the power off and on. If the problem persists, contact your local distributor.
1001 Ethernet I/F unit not ready
1002 Ethernet I/F unit DPRAM error
1003 No response from Ethernet I/F unit
1004 Ethernet receive buffer over
1005 Ethernet send registration error
1006 I/F unit unregistered interrupt
1100 to 1115 Initialization error (communication unit)
1120 Dual port access error
1200 Undefined register
1201 Send/receive buffer area over
1202 MAC address error
1203 Port error Check whether the Ethernet I/F unit is mounted correctly, and then turn the power off and on. If the problem persists, contact your local distributor.
1301 Watch dog overflow
1302 JAVA error LANC error