V6 |
Error No. |
Contents |
Remedies |
O |
O |
3 |
The screen data version does not match the system program version of MONITOUCH. | Transfer the system program from the V-SFT editor. If not solved, check the V-SFT editor version and the system program version and contact your local distributor. |
O |
O |
10 |
The I/F board and the communication driver software do not match. | Check the driver and transfer again. |
O |
O |
11 |
The PLC for data setting does not match the I/F driver. | Check the PLC model and transfer the I/F driver again. |
O |
O |
12 |
The version of the I/F driver does not match the version of data. | Check the V-SFT editor version and the I/F driver version and contact your local distributor. |
O |
O |
13 |
The version of the I/F driver does not match the version of the V series. | Check the I/F driver version and the system program version and contact your local distributor. |
O |
O |
15 |
The display language of the V series does not match the language used for the created data. | Check the MONITOUCH model and the language used for the created data. |
O |
O |
17 |
Unknown network I/O No. The I/O number exceeds the possible range of use. | Reset to a number that falls in the possible range of use. |
O |
O |
18 |
When connected to “1 : n,” the read area, write area, and calendar memory settings are all made in the internal memory. | Set the read area and the calendar memory on the PLC. |
O |
O |
20 |
The maximum 32K-word capacity for the buffering area has been exceeded. (Internal buffer) | Correct the data size so that the buffering area falls within the 32 k words limit. |
O |
O |
21 |
The maximum 128-word capacity for bit sampling has been exceeded. | Reduce the total number of words for bit sampling to less than 128 words. |
O |
O |
22 |
The buffer number specified in the sampling mode has not been set. | Set the buffer number in the [Buffering Area Setting] dialog under [System Setting]. |
O |
O |
23* |
Memory card file No. error | Contact your local distributor. |
O |
O |
24 |
When [Store Target: SRAM/CF Card] is selected in the [Buffering Area Setting], the output file number can be set. However, the set output file number already exists. Or, [Type: Buffering File] is not set in the [Memory Card Setting] dialog though [Store Target: SRAM/CF Card] is selected. | Check the output file number in the [Buffering Area Setting] dialog, and set correctly. Or, check the setting in the [Memory Card Setting] dialog. |
O |
O |
28 |
The modular function is set as the same communication port as MJ1 and MJ2. | Check the setting in the [Modular Jack] dialog and set correctly. |
O |
O |
30 31 |
The number of registered items is too many. | Reduce the number of items. |
O |
O |
32 |
The number of items that uses the memory exceeds the available number. | Reduce the number of items. |
O |
O |
33 |
The number of switches set on the screen exceeds the maximum (V7 series/ V608/ V610/ V612: 768, V606/ V606i: 192). Overlap switches and lamps are included in this number. | Reduce the number of switches and lamps. |
O |
O |
34 |
The items that use the memory exceeds the available work memory. | Reduce the amount of data. |
O |
O |
39 |
The amount of data for one screen exceeds 256 kbytes (V6: 128 kbytes). | Reduce the amount of data. |
O |
O |
40* |
Group byte count error | Contact your local distributor. |
O |
O |
41* |
Recognition flag error | |
O |
O |
42* |
Function ITEM error | |
O |
O |
43* |
Function ITEM end error | |
O |
O |
44* |
Group ITEM end error | |
O |
O |
45* |
Offset range over | |
O |
O |
46 |
Memory setting error (Unavailable memory/memory range over) | Check the memory setting. |
O |
O |
47 |
The division number of the item limited to setting on a screen library is duplicated on a screen. | Check the division number and avoid duplication. |
O |
O |
52 |
Overlap No. error A number other than 0 to 2 is set. | Check the overlap number and set correctly. |
O |
O |
53 |
In the setting for call-overlap, an overlap number that is not registered in multi-overlap edit has been specified. | Specify an overlap number registered in multi-overlap edit. |
O |
O |
54 |
The overlap occupies too much memory capacity. (Refer to “Chapter 2 Overlap.”) | Reset the overlap data size. |
O |
O |
55* |
Multi-overlap header error | Contact your local distributor. |
O |
O |
56* |
Graphic undefined command error | |
O |
O |
57* |
Graphic ITEM error | |
O |
O |
58* |
Graphic execution error | |
O |
O |
59* |
Switch function error | |
O |
O |
60 |
Switch operating area error | Reset the switch operating area. |
O |
O |
61* |
Statistic graph % display No. over | Contact your local distributor. |
O |
O |
62* |
Multi data over | |
O |
O |
63 |
The selection order number of data blocks (a maximum of four) is duplicated. | Check the data block selection order number and set correctly. |
O |
O |
64* |
Data display element No. error | Contact your local distributor. |
O |
O |
65 |
The scale or graph is not set correctly in the settings for trend graphs or trend sampling. | Correct the settings for both [Scale Max. Value] and [Scale Min. Value] or both [Graph Max. Value] and [Graph Min. Value] in the dialog. |
O |
O |
66* |
Internal circle radius is 0. | Contact your local distributor. |
O |
O |
67* |
The number of trends ≤ 0 | |
O |
O |
68 |
The display area is insufficient for the area (lines) that is displayed by one relay (one bit). | Check the [Lines/Relay] in the [Relay] dialog and enlarge the display area if necessary. |
O |
O |
69 |
A pattern size larger than the screen has been specified. | Re-set the pattern. |
O |
O |
70 |
Data sheet: column/line over | Check the data sheet columns/lines, and set correctly. |
O |
O |
71 |
The parts for a closed area graph exceed 64 kbytes (V606: 32 kbytes). | Reduce the size of the parts. |
O |
O |
72 |
Bit sampling mode with [ Real Time Print] are over 4. Or, there are more than two bit sampling modes that have the same [Buffer No] with [ Real Time Print]. | Specify the setting of [ Real Time Print] according to the limits of setting. If not solved, check the V-SFT editor version and the system program version and contact your local distributor. |
O |
× |
73 |
Video item setting number error There are four or more vide items on one screen. (including the screen library) | Check the number of video items and reduce the number. |
O |
× |
74 |
Animation item is placed somewhere other than the base screen (screen library, etc.). | Place the animation item on the base screen. |
O |
× |
75 |
The screen data type is not consistent. 128-color data is transferred to MONITOUCH of 32k colors. Or, 32k-color data is transferred to MONITOUCH of 128 colors. | Transfer the system program from the V-SFT editor. |
O |
O |
80* |
Macro: undefined command error | Contact your local distributor. |
O |
O |
81 |
Macro: FOR-NEXT command number is wrong. | Correct the FOR-NEXT command. |
O |
O |
82 |
Macro: There are two different commands for the same label number. | Delete or correct the label command being used for two different commands. |
O |
O |
83 |
Macro: There is no destination label for the jump. | Change or create the destination label. |
O |
O |
84 |
Macro: Invalid memory | Change the macro. |
O |
O |
85* |
Macro: undefined system call | Contact your local distributor. |
O |
O |
90 |
You attempted to use a screen library that is not registered. | Check the screen library number. |
O |
O |
91 |
Switch/lamp bitmap unregistered | Check the following points. • No bitmap name is designated. • The total of 3D parts exceeds 1023 (maximum). • The part size is too large. • There is no bitmap in the PARTS folder. |
O |
O |
92* |
Multi-language initial display string No. error | Contact your local distributor. |
O |
O |
93* |
Multi-language message group count error | |
O |
O |
94 |
Multi-language selection string number error | |
O |
O |
95 |
MR400 format table String code error | There is an illegal code after “\” in the string. |
O |
O |
96 |
MR400 format table String size error | The total size of the string is too large. |
O |
O |
97 |
Multi-language font setting error | Transfer the first language font or screen data again. |
O |
O |
100 |
Universal serial GD-80 compatibility is set in entry mode. | Uncheck [GD-80 Compatible] in entry mode. |
O |
O |
101 |
Universal serial System memory setting error | Check whether or not access to outside the specified memory is attempted, such as for macro indirect designation. |
O |
O |
102 |
Connection type setting error | Check the setting for [Connection] in the [Comm. Parameter] dialog. |
O |
O |
103 |
Network I/O size setting error | Check the number of words set for [No. of Works Setting for I/O] in the [Comm. Parameter] dialog. |
O |
O |
104 |
Network table setting error | Check the setting on the network table. |
O |
O |
120 |
[Multi-Link] is not selected at [Modular Jack 1 (or 2)] in the case of [Connection: Multi-Link2]. | [Select [Multi-Link] at [Modular Jack 1 (or 2)]. |
O |
O |
121 |
[Multi-link2] port number error. The value for [Local Port] or [Total] is out of the range of 1 to 4. | Set the value of [Local Port] or [Total] within the range of 1 to 4. |
O |
O |
130* |
[Ethernet] Network byte error | Contact your local distributor. |
O |
O |
131 |
[Ethernet] The local port is not set in the table. | Check the port number of the I/F unit, and check that the local port is set on the network table edit window. |
O |
O |
132* |
[Ethernet] [DNA] The network table is not found or is not the right one. | Contact your local distributor. |
O |
O |
133 |
[Ethernet] IP address No. error | Check the IP address on the network table edit window. |
O |
O |
134 |
[Ethernet] Port No. error | Check the port number on the network table edit window. |
O |
O |
135 |
[FL-net] FL-net data error | Check the setting for [FL-Net] in the [Comm. Parameter] dialog. |
O |
O |
140 |
[Temp. control network/PLC2Way] The version of the temperature control/PLC2Way driver does not match the version of the system program. | Check that the system program version is compatible with the temperature control network/PLC2Way function, and if necessary, update the system program version. |
O |
O |
141 |
[Temp. control network/PLC2Way] Multi-link 2 connection is set. (communication parameter setting) | It is not possible to use multi-link 2 connection and temperature control network/PLC2Way function at the same time. |
O |
O |
142 |
[Temp. control network/PLC2Way] The temperature control/PLC2Way driver is not found. | Transfer the temperature control/PLC2Way driver. |
O |
O |
143 |
[Temp. control network/PLC2Way] The temperature control network/PLC2Way table is not set. | Check the temperature control network/PLC2Way table and set correctly. |
O |
O |
144 |
[Temp. control network/PLC2Way] No modular setting is made. | Check the modular setting for the temperature control network/PLC2Way function. |
O |
O |
145 |
[Temp. control network/PLC2Way] The temperature control network/PLC2Way table is duplicated. | Check that the table number is not duplicated in the [Buffering Area Setting] dialog, and set correctly. |
O |
O |
146* |
[Temp. control network/PLC2Way] Temperature control network/PLC2Way table setting memory error | Contact your local distributor. |
O |
O |
147 |
[Temp. control network/PLC2Way] The model of the temperature controller/PLC2Way does not match the driver. | Bring up the Main Menu screen → [Extension], and check the version. If necessary, transfer screen data or the temperature control/PLC2Way driver. |
O |
O |
155 |
FROM data unregistered The default.dtm file is not transferred when [ Use Internal Flash ROM as Back-up Area] is checked in the [Unit Setting] dialog. Or no port number table is found though [ Use Station Number Table] is checked for temperature control network. | When this item is checked, the screen data capacity of the Main Menu screen becomes 128 kbytes smaller than the case when it is not checked. Check the setting. If the capacity is not reduced, contact your local distributor. |
O |
O |
156 |
Both [ Use Internal Flash ROM as Back-up Area] in the [Unit Setting] dialog and [ Use Station Number Table] for the temperature control network are checked. | It is not possible to use both functions at the same time. Uncheck either item, and transfer screen data again. |
O |
O |
157 |
[Temp. control network/PLC2Way] Port numbers in the port number table are duplicated. | Be sure to avoid port number duplication when the port number table is changed by the FROM_WR macro command. |
O |
O |
160 |
The SRAM area size exceeds the available range. Cassette: 256 k words Built-in: 32 k words | Check the setting in the [SRAM/Clock Setting] dialog. |
O |
O |
161 |
The SRAM area is not formatted. | Format the SRAM area on the “SRAM/Clock” screen that can be displayed from the Main Menu screen. Check that the battery voltage is not lowered. |
O |
O |
162 |
Data in the SRAM area does not match the system program version. | Check the system program version, and contact your local distributor. |
O |
O |
163 |
The setting in the [SRAM/Clock Setting] dialog does not match the SRAM area format. | Format the SRAM area on the “SRAM/Clock” screen that can be displayed from the Main Menu screen. |
O |
O |
170 |
The ladder communication program does not exist in the V series though [Ladder Tool] is selected for [Modular Jack] for the screen data. | When ladder transfer is not performed, uncheck [Ladder Tool] for [Modular Jack 1 (or 2)]. To perform ladder transfer, transfer the “MelQHCpQ.lcm” program to the V series. |
O |
O |
171 |
The PLC model set for screen data does not match the model of the ladder communication program. | Transfer the ladder communication program for the PLC model. (Available with Mitsubishi QnHCPU port (Q) only) |
O |
O |
172 |
A ladder communication program is stored in the V series though [Ladder Tool] is not set for [Modular Jack] for the screen data. | Check [Ladder Tool] for [Modular Jack\ for the screen data. |
O |
O |
173 |
A connection other than [1 : 1] is selected in the [Comm. Parameter] dialog though [Ladder Tool] is set for [Modular Jack] for the screen data. ([1 : 1] must be selected for ladder transfer.) | When ladder transfer is not performed, uncheck [Ladder Tool] for [Modular Jack 1 (or 2)]. To perform ladder transfer, select [1 : 1] for [Connection] in the [Comm. Parameter] dialog. |
O |
O |
174 |
UNIPLC is set for the I/F driver. (Ladder transfer is not supported on the simulator.) | Uncheck [Use Simulator] in the [Transfer] dialog before transferring the screen data. |
O |
O |
180 |
The MODBUS slave communication program is not found. | Transfer the screen data again. |
O |
O |
181 |
The slave communication program is stored in the V series though [Modbus Slave Table is not set for [Modular Jack] for the screen data. | Select [Modbus Slave Table] for [Modular Jack] for the screen data. |
O |
O |
182 |
[Modbus Slave Table] and [V-Link] are selected for [Modular Jack] for the screen data. | It is not possible to use slave communication and V-link connection at the same time. |
O |
O |
201* |
Total byte count error | Contact your local distributor. |
O |
O |
202 |
The setting of [System Setting] → [Unit Setting] → [Touch Switch] is not correct. | Select the touch switch type appropriate for the V series. |
O |
O |
203 |
Select the touch switch type appropriate for the V series. | Delete the item (= memo pad). |
O |
O |
204 |
Manual setting font is not transferred. Strings equivalent to auto setting font are displayed correctly, however, if not, they are tentatively displayed in 12-point font. | Check the manual font setting, and transfer the screen data again. |
O |
O |
205 |
SRAM cassette is not mounted. Attach the SRAM cassette. × 206 Option unit “EU-0 ” is not mounted. | Attach the SRAM cassette. |
O |
O |
206 |
Option unit “EU-0x” is not mounted. | Attach the option unit “EU-0x” |
O |
O |
207 |
Option unit “EU-00” is not mounted. | Attach the option unit “EU-00.” |
O |
O |
208 |
There is no gateway setting. | To use the e-mail function, be sure to set gateway on the network table (Ethernet). |